Van Probe Thermo Anemometer
PERFORM A MEASUREMENT
Turn on the de device by pressing on On/Off/Esc .
The device displays its name LV110 , LV111 or LV117 .
Put the probe to the required location.
The device displays the velocity and temperature measurement.
FREEZE THE MEASUREMENT
During a measurement :
Press once on Hold/min/max .
Hold appears on screen and the measurement is frozen.
Press on On/Off/Esc to exit the hold function.
The device returns to the measurement display.
DISPLAY THE MINIMUM AND THE MAXIMUM
Once the measurement is frozen :
Press on Hold/min/max .
The device displays the maximum value of velocity or airflow measured since the last questioning at the top of the screen and the minimum value of velocity or airflow measured since the last questioning at the bottom of the screen.
Press again on Hold/min/max .
The device displays the maximum value of temperature measured since the last questioning at the top of the screen and the minimum value of temperature measured since the last questioning at the bottom of the screen.
Press on On/Off/Esc to return to the measurements display.
PERFORM AN AVERAGE IN VELOCITY
The device is on and displays the measurement.
Press on OK . START displays on screen.
Press on OK ,the average calculation is launched, END displays on screen, AVG blinks.
Press on OK to stop the calculation, the average displays.
Press on OK to display the maximum and minimum values measured during the calculation of this average.
Press on On/Off/Esc to exit the average function and return to the measurements display.
DISPLAY AND MEASURE THE AIRFLOW
It is possible to display and to measure the airflow in place of the velocity. The device is on and displays the velocity and temperature measurements.
Press on Select .
MODE blinks on screen.
Press on OK .
VELO blinks at the bottom of the screen.
Press on Select to select the FLOW mode then press on OK to validate.
Depending on the device type, CIRC , K 25 85 , CONE or RECT blinks at the bottom of the screen.
Press on Select to select rectangular RECT , CIRC , K 25 85 (LV110) or CONE (LV111) for a measurement with an airflow cone then press on OK .
If RECT or CIRC is selected, the measuring unit of the type of duct displays.
Press on Select to select the unit : mm or inch then press on OK to validate.
If the type of selected duct is circular : DIAM displays and the first digit blinks. Press on Select to select its value then press on OK to validate. Perform the same procedure to select the values of the following digits (to return to the previous digit press on On/Off/Esc ). When the last digit is adjusted, press on OK to validate. The device returns to the display of airflow and temperature measurements.
If the type of selected duct is rectangular : LENGT displays on screen and the first digit blinks. Press on Select to select its value then press on OK to validate. Perform the same procedure to select the values of following digits (to return to the previous digit press on On/Off/Esc ). When the last digit is adjusted, press on OK . WIDTH to adjust the width displays on screen, perform the same procedure to select the digits value, when the last digit is adjusted, press on OK to validate. The device returns to the display of airflow and temperature measurements.
If K 25 85 is selected (LV110): the device returns to the measurements display.
If CONE is selected (LV111): CONE displays on screen and the cone type blinks : K35, K75, K120, K150. Press on Select to select the type of cone, then press on OK to validate. The device returns to the display of airflow and temperature measurements.
Technical Specification :
LV 110 | ||
Sensor | Min | Max |
Air velocity | 0.30 m/s | 35.00 m/s |
LV 111 | ||
Sensor | Min | Max |
Air velocity | 0.80 m/s | 25.00 m/s |
LV 117 | ||
Sensor | Min | Max |
Air velocity | 0.40 m/s | 35.00 m/s |
LV 110- LV111-LV 117 | ||
Sensor | Min | Max |
Airflow | 0.00 m/h | 99999.00 m/h |
Temperature | -20.00 C | 80.00 C |
Technical details :
Parameters | Air velocity Airflow Temperature |
Displays | 4-line display |
IP Protection | IP 54 |
Battery life | 58 hours |
Standards | 2011/65/EU RoHS II |
Power supply | 4 batteries AAA LR03 1.5 V |
Anemometer type | Vane |
Probe type | Wire probe |
Protective cover | No |
Interchangeable module | No |
Instrument Dimensions : | |||
Length | Width | Height | Weight |
76.70 mm | 34.20 mm | 147.90 mm | 390.00 g |
Operating temperature | |||
Min | Max | ||
0.00 oC | 50.00 oC | ||
Storage temperature | |||
Min | Max | ||
-20.00 oC | 80.00 oC |